BACKPRESSURE COMPENSATED AIR BALANCE SYSTEM. DIRECT DIGITAL READOUT IN ENGLISH AND METRIC UNITS. Measured in cubic feet per minute (cfm) and litres per second (L/s) corrected for local air density.
The measurement range is 25-2500 cfm supply and 25-1500 cfm exhaust. Accuracy is ±3% of reading ±7 cfm from 100 to 2000 cfm.The air density correction range is 14-40 in Hg and 32ºF to 158ºF for correction of air flow measurements. The readings represent local density airflow corrected for the density effects of temperature and absolute pressure. Five seconds for air flows greater than 180 cfm, and up to eight seconds at less than 70 cfm. 10 digit, 0.4, high contrast, liquid crystal display. FlowHood unit with meter and 2'x2 top, 9.7 lbs.
Height 40"; top 24"x24"; base 14"x14. 3000 readings per charge, 500 recharge cycles. The item "Shortridge CFM-88 Airdata Multimeter Flow Meter WITH HOODS Air Balance System" is in sale since Saturday, June 1, 2019. This item is in the category "Business & Industrial\Test, Measurement & Inspection\Test Meters & Detectors\Air Flow & Anemometers". The seller is "2ninternationale" and is located in Vaulx en Velin.